SERVICE PROCEDURES FOR FIRE EXTINGUISHING EQUIPMENTS 1. Portable Fire Extinguishers
- Check outside condition for body, handle, hose & nozzle, valve. Repair if necessary. - Check Agent and propellant Gas. Replace if necessary. - Check Hydrostatic Test Date. Re-test if expired. - Put on label with inspection date and inspection card - Make report and issue Certificate
2. High Pressure CO2 system
* Annual inspection - Inspection / check weight of CO2 cylinder - Check audible / visual alarm system, fan stop - Blowing by compressed air from CO2 room to all nozzles
* 5 yearly inspection - Inspection / test Time Delay Unit - Manifold leakage tested by applying dry working air - Pilot line pressure tested at maximum working working pressure - Internal inspection for main valve
* 10 yearly inspection - Pressure test CO2 cylinder (at least 10%) - Replace flexible hose (if applicable)
3. Self Contained Breathing Apparatus (SCBA) - Check / clean hardness, facemask, breathing valve, pressure gauge - Check condition of air cylinder with valve. Refilling if necessary - Attach label with inspection date
|
|
||||||
PHANTA TRADING & TECHNICAL SERVICES LTD. |
|||||||
391 Dao Tri St, Dist. 7, Ho Chi Minh City, Vietnam |
|||||||
Phone: (84-8) 3773 4498 Fax: (84-8) 3773 4464 |
|||||||